27 August 2013
In addition to decoupling, continuous monitoring is also important. In order to detect critical operating states early on, the modules provide information on the output voltages of the power supply units, defects in the wiring or decoupling section, and the present load current. Permanently monitoring the load current offers an important advantage when expanding or upgrading systems. If additional loads are connected to a redundant power supply when expanding the plant or system, this can result in a loss of redundancy. The system operator will immediately be aware of a loss of redundancy as the Oring module signals the overload condition.The ACB (Auto Current Balancing) technology is said to double the service life of the redundant power supplies, ensuring that both units work under the same load. The load current is automatically distributed in a balanced manner. The 1 x 20 A, 1 x 40 A, and 1 x 80 A modules are suitable for DC voltages of 18 to 30 V. The 32, 38, and 66 mm wide units are simply snapped into place on the mounting rail.