• Unregulated Power Supply: Exceeding the maximum 30Vdc to the Hall Effect sensor will damage the unit. A good quality regulated DC power supply is recommended for powering a pulse flow meter.
• Electrical Interference / Voltage Spikes: Other connected equipment containing inductors (coils), or electromagnetic components (such as solenoid valves or pumps) can produce high voltage spikes when switching. These spikes can be a hundred to thousands of volts and if on the same circuit, will damage the flowmeter sensor beyond repair.
Electrical interference can also occur even without a direct connection if cabling is routed close to high-power equipment.
A failure mode that is commonly seen, is where a simple solenoid valve is operated on the same power supply as the flowmeter. When the solenoid de-energises in 1ms it produces a spike of 100s of Volts. Some of this voltage spike feeds through to the sensor, momentarily exceeding the 30Vdc maximum of the sensor causing it to fail.