This website uses cookies primarily for visitor analytics. Certain pages will ask you to fill in contact details to receive additional information. On these pages you have the option of having the site log your details for future visits. Indicating you want the site to remember your details will place a cookie on your device. To view our full cookie policy, please click here. You can also view it at any time by going to our Contact Us page.

Diagnostics-enabled safety relays

04 June 2018

The new KFD2-RSH safety relays from Pepperl+Fuchs combine a diagnostic function, line fault transparency, and dual redundancy in a one-out-of-three architecture.

During each switching operation, the function of the switching contacts is automatically checked. This reduces the effort required for proof testing. Thanks to line fault transparency, the entire signal circuit can be monitored for line faults without the need for additional wiring. The relays are immune to test pulses and are therefore compatible with digital output cards for all common control panels.

The one-out-of-three architecture with dual redundant switching contacts is at the core of the new modules. For de-energized-to-safe (DTS) applications, there are three serial contacts. For energized-to-safe (ETS) signal circuits, there are two groups of three contacts each, arranged in parallel. The safety function is ensured, even if up to two contacts in a group fail.

The integrated diagnostics function moves the three contacts successively with a time delay during each switching operation. In ETS applications, all three relays of both contact groups are initially closed with three consecutive switching events. During the delay period, the device checks whether this contact closes the circuit and detects any faulty circuits.

DTS device diagnosis takes place during the restart process. Initially, two relay contacts are closed simultaneously, then the third contact is closed after a time delay. The idea is that there is no current flowing before the third contact closes, otherwise this relay is defective because it no longer disconnects the circuit. Another relay is checked during every switching cycle.

After switching three times, the relay module is fully tested once without any additional effort. The diagnostics results are provided:
• via the LED on the module
• as a collective error message on the power feed module
• by evaluating the test pulses from the control panel
• on the additional relay output

Short circuits and lead breakages can also be detected on the field side through the control system's digital output card (DO card) and assigned to a specific signal circuit. No additional wiring is required. The single-channel devices are certified in accordance with the ATEX/IECEx Zone 2 and UL standards and are suitable for DTS and ETS applications up to IEC61508 SIL 3. The DTS modules are also suitable for applications up to EN ISO 13849 PL e